The complex power associated with each phase of a balanced load is 144 + j192 kVA. The line voltage at the terminals of the load is 2450 V. A balanced bank of delta- connected capacitors is connected in parallel with the load. The circuit is operating at a frequency of 60 Hz. The capacitors are adjusted so that the magnitude of the line current feeding the parallel combination of the load and capacitor bank is at its minimum.
1. What is the size of each capacitor in microfarads?
2. Repeat (a) for wye connected capacitors.
3. What is the magnitude of the line current?
Answers: 3
Physics, 22.06.2019 12:00
An architect plans to use solar energy to heat the next house he designs. what principle of absorption and infrared energy can be applied to the design of the new house? how could she apply to those principals?
Answers: 2
Physics, 22.06.2019 13:30
Global warming will produce rising sea levels partly due to melting ice caps but also due to the expansion of water as average ocean temperatures rise. to get some idea of the size of this effect, calculate the change in length of a column of water 1.00 km high for a temperature increase of 1.00ºc. note that this calculation is only approximate because ocean warming is not uniform with depth. (answer in ×10^{-3} −3 m)
Answers: 1
The complex power associated with each phase of a balanced load is 144 + j192 kVA. The line voltage...
Mathematics, 11.06.2020 23:57
Mathematics, 11.06.2020 23:57
Mathematics, 11.06.2020 23:57
Mathematics, 11.06.2020 23:57
Mathematics, 11.06.2020 23:57
Mathematics, 11.06.2020 23:57
Physics, 11.06.2020 23:57
Mathematics, 11.06.2020 23:57
History, 11.06.2020 23:57
Mathematics, 11.06.2020 23:57
Mathematics, 11.06.2020 23:57
Mathematics, 11.06.2020 23:57